String voltage calculator (Voc)

Panel voltage rises as the panel gets colder. Enter your panel and your charge controller or inverter, and this works out the voltage on the coldest morning of the year and how many panels can go in one string.

Open-circuit voltage, from the panel's datasheet.
From the same datasheet, in %/°C. It's a negative number.
The coldest your site gets, in °C.
From its datasheet, in volts.
Optional. Fill it in to check a string you've already planned.
See your result
– V
per panel, at the design temperature
The two ways Rule 64-202 allows
RouteV per panelMost panels
× 125%––
Coefficient––

Fill in the first four figures.

Show the arithmetic
–

This gives the most panels a string can take, and nothing else. A string that passes here still has to stay above the controller's start voltage on a hot summer day, and the cable, disconnects and fuses all take their voltage rating from the figure above. That figure also goes on the permanent marking at the disconnect.

Both routes are permitted. The × 125% factor is built on a panel temperature of −40 °C. The coefficient route uses your panel and your site, and usually allows a longer string. The arithmetic is shown above so you can check it.

Not sure your string fits? Bring the panel model, the controller or inverter, and the coldest temperature your site sees to the counter, or call 587-287-9180. More on this in Solar panels in an Alberta winter.

Code: Canadian Electrical Code, Part 1, Rules 64-200 and 64-202.